  Single Phase Motor Full Load Amps Table
 
Full Load Amperes
Horsepower 115 V 208 V 230 V Minimum
Transformer
KVA
1/6 4.4 2.4 2.2 .53
1/4 5.8 3.2 2.9 .70
1/3 7.2 4.0 3.6 .87
1/2 9.8 5.4 4.9 1.18
3/4 13.8 7.6 6.9 1.66
1 16 8.8 8 1.92
1-1/2 20 11 10 2.40
2 24 13.2 12 2.88
3 34 18.7 17 4.10
5 56 30.8 28 6.72
7-1/2 80 44 40 9.6
10 100 55 50 12
(1) When motor service factor is greater than 1, increase full load amps proportionally.
     Example: If service factor is 1.15, increase above amp values by 15%.
Note: If motors are started more than once per hour add 20% additional KVA.
(Table by Acme Electric Corporation).